The DAT-040-12-02 is a thermoelectric based air conditioner designed to temperature control small chambers used in analytical and medical diagnostic instruments. The unique design offers premium fans pushing air across-high density heat sinks to minimize the number of air flow paths required to operate. The design utilizes custom thermoelectric modules to maximize cooling capacity with a high coefficient of performance. Moisture resistant insulation is used to keep condensation from penetrating the TEM cavity. The unit operates on DC and is designed for an indoor lab use environment. It has a maximum Qc of 37.4 Watts when ΔT = 0 and a maximum ΔT of 42 °C at Qc = 0.
Electrical and Thermal Performance Curves
Select Graph
Y - Axis
Select Graph
X - Axis
Electrical Operating Points
Selected Operating Point
Cooling Power (Qc) = Watts
TEM Voltage = Volts
TEM Current = Amps
TEM COP =
Power Supply = Watts
Power Dissipated (Qh) = Watts
Thot = °C
Fan Voltage = 12.0 Volts
Fan Current = 0.5 Amps
Cooling Power (Qc) = Watts
TEM Voltage = Volts
TEM Current = Amps
TEM COP =
Power Supply = Watts
Power Dissipated (Qh) = Watts
Thot = °C
Fan Voltage = 12.0 Volts
Fan Current = 0.5 Amps
Optimum COP
Cooling Power (Qc) = 10.4 Watts
TEM Voltage = 7.6 Volts
TEM Current = 1.6 Amps
TEM COP = 0.9
Power Supply = 12.1 Watts
Power Dissipated (Qh) = 22.49 Watts
Fan Voltage = 12.0 Volts
Fan Current = 0.5 Amps
Cooling Power (Qc) = 10.4 Watts
TEM Voltage = 7.6 Volts
TEM Current = 1.6 Amps
TEM COP = 0.9
Power Supply = 12.1 Watts
Power Dissipated (Qh) = 22.49 Watts
Fan Voltage = 12.0 Volts
Fan Current = 0.5 Amps
Maximum Qc
Cooling Power (Qc) = 27.8 Watts
TEM Voltage = 19.8 Volts
TEM Current = 4.3 Amps
TEM COP = 0.3
Power Supply = 85.6 Watts
Power Dissipated (Qh) = 113.4 Watts
Fan Voltage = 12.0 Volts
Fan Current = 0.5 Amps
Cooling Power (Qc) = 27.8 Watts
TEM Voltage = 19.8 Volts
TEM Current = 4.3 Amps
TEM COP = 0.3
Power Supply = 85.6 Watts
Power Dissipated (Qh) = 113.4 Watts
Fan Voltage = 12.0 Volts
Fan Current = 0.5 Amps
* Any information furnished by Laird Thermal and its agents is believed to be accurate and reliable. All specifications are subject to change without notice.
Specifications
Operating Temperature Range
-10 °C - 50°C ( 14 °F - 122°F )
Supply Voltage
12.0 VDC nominal / 15.0 VDC maximum
Current Draw
2.9 A running / 3.4 A startup
Power Supply
38.0 Watts
Performance Tolerance
10%
Fan MTBF
50,000 hours
Weight
0.80 kg ( 1.76 lbs )
Mounting Hole Location
Wiring Schematic
Notes
1For indoor use only