Thermal Wizard - Thermoelectric Assemblies Datasheet


AA-150-24-22

Overview: PowerCool Series
The AA-150-24-22 is an Air-to-Air Thermoelectric Assembly (TEA) that uses impingement flow to transfer heat. It offers dependable, compact performance by cooling objects via convection. Heat is absorbed and dissipated through high density heat exchangers equipped with air ducted shrouds and brand name fans. The heat pumping action is created by thermoelectric modules, which are custom designed to achieve a high coefficient of performance (COP). It has a maximum Qc of 137.5 Watts when ΔT = 0 and a maximum ΔT of 36 °C at Qc = 0.

Electrical and Thermal Performance Curves

Select Graph
Y - Axis




Select Graph
X - Axis


Imin: 2.8 A
Imax: 10.6 A

Vmin: 10.3 V
Vmax: 34.5 V
Voltage 
Current  
Click UPDATE to view changes in thermal operating conditions
Control Temp  
Ambient Temp  
Δ T  


Electrical Operating Points
Selected Operating Point
Cooling Power (Qc) = Watts
TEM Voltage = Volts
TEM Current = Amps
TEM COP =
Power Supply = Watts
Power Dissipated (Qh) = Watts
Thot = °C
Fan Voltage = 24.0 Volts
Fan Current = 1.1 Amps
Optimum COP
Cooling Power (Qc) = 38.5 Watts
TEM Voltage = 16.8 Volts
TEM Current = 5.0 Amps
TEM COP = 0.5
Power Supply = 83.7 Watts
Power Dissipated (Qh) = 122.19 Watts
Fan Voltage = 24.0 Volts
Fan Current = 1.1 Amps
Maximum Qc
Cooling Power (Qc) = 79.6 Watts
TEM Voltage = 34.5 Volts
TEM Current = 10.6 Amps
TEM COP = 0.2
Power Supply = 363.9 Watts
Power Dissipated (Qh) = 443.5 Watts
Fan Voltage = 24.0 Volts
Fan Current = 1.1 Amps


* Any information furnished by Laird Thermal and its agents is believed to be accurate and reliable. All specifications are subject to change without notice.


Specifications
Operating Temperature Range
-10 °C - 48°C  ( 14 °F - 118°F )
Supply Voltage
24.0 VDC nominal / 27.0 VDC maximum
Current Draw
7.9 A running / 9.0 A startup
Power Supply
190.0 Watts
Performance Tolerance
10%
Fan MTBF
40,000 hours
Weight
7.90 kg ( 17.42 lbs )

Mounting Hole Location
Wiring Schematic

Notes
1For indoor use only
2Units are generally maintenance free, however occasionally it is recommended to clean the heat sinks and fans of debris. This is best done with compressed air.

AA-150-24-22